Q : How to Troubleshoot Bus Overvoltage, UPS Failure, and Output Overload in HT33 and RM Series UPS Systems?
A: These series HT3360-500K,RM20-90K(PM10-15K)RM25-600K(PM30X),RM25-200K(PM25C),RM40-500K(PM50),RM600/60D,RM600-1000K(PM100DFaults such as bus overvoltage, explosion, and output overload occur.
To check the "Scope" menu on the display, look at the output voltage and current waveforms. To zoom in on the current waveform, click "Zoom In" when it is displayed in Small mode.
The purpose is: to see the type of load, whether it is industrial control load, because industrial control load has energy feedback to the UPS, causing unstable operation.
The current solution is to install the BAU (discharge device).