Q : What Precautions Should Be Taken When Connecting a BAU to a UPS?
A: Precautions for using BAU (Back-feed Absorbing Unit ) to connect UPS:
1. Due to the current limitation of the UPS cabinet back board, only one interface of one BAU can be connected to the module back board of one UPS cabinet.
2. It is recommended to connect the working input terminal of BAU to the output N terminal of UPS, rather than the main input N terminal of UPS, to prevent the disconnection of the N wire in the UPS circuit (such as turning off the output switch of UPS, the N wire of UPS will be disconnected), which may cause interruption of the N wire on BAU and result in abnormal voltage sampling of BAU, causing damage to BAU during operation.
3. The standard voltage version of BAU is currently applicable to power modules of PM25X, PM30X, PM40X, and PM50X.
Related Questions
What causes the UPS to frequently trigger charging and discharging alarms?
How to Troubleshoot RMX Series UPS Module Cabinet Detection Failure?
How to Troubleshoot the “Rectifier Fail-SET / REC Soft Start Fail-SET” Alarm on RM/50X UPS?
More Resources

Services
Learn about INVT’s global after-sales policies, service processes, and technical support commitment.

Downloads
Get product catalogs, manuals, drawings, software, certificates, and more.

Training Videos
Learn product knowledge, operation guides, and application technologies through online training videos.



Repair Progress Tracking | Identity Verification
To protect your repair information, please verify using the mobile number reserved on the service order.

Contact INVT
Get in touch with INVT. Our team will get back to you shortly.
-
Industrial Automation
-
Network Power
-
PV & ESS
-
e-Mobility