What Precautions Should Be Taken When Connecting a BAU to a UPS?

Q : What Precautions Should Be Taken When Connecting a BAU to a UPS?

Views : 16
2026-11-20

A: Precautions for using BAU (Back-feed Absorbing Unit ) to connect UPS:

1. Due to the current limitation of the UPS cabinet back board, only one interface of one BAU can be connected to the module back board of one UPS cabinet.

2. It is recommended to connect the working input terminal of BAU to the output N terminal of UPS, rather than the main input N terminal of UPS, to prevent the disconnection of the N wire in the UPS circuit (such as turning off the output switch of UPS, the N wire of UPS will be disconnected), which may cause interruption of the N wire on BAU and result in abnormal voltage sampling of BAU, causing damage to BAU during operation.

3. The standard voltage version of BAU is currently applicable to power modules of PM25X, PM30X, PM40X, and PM50X.