How can the DA807 SNMP card display the input and output three-phase current, battery current, active and reactive power, etc.?
A: 1.Connect the DA807 SNMP card to the UPS and enter the main page.
2. Enter the UPS configuration page and set the correct protocol. For 3/3 machines, select MegaTec Three phase (3 input - 3 output); for 3/1 machines, select MegaTec Three phase (3 input - 1 output).
3. Return to the main page and click the main path input icon to display the input parameter information.
4. The operation steps for the battery and output information are the same as above.
When using the analog input to control the frequency, the system fails to detect 10Hz. If set to 10Hz, the AI shows 0%; if set to 25Hz, the AI shows 32%; if set to 40Hz, the AI shows 87%; if set to 50Hz, the AI shows 99%. How should it be adjusted?
A: In the MVDP5 group parameters, select to adjust the accuracy of AI1 to control the accuracy of the analog input.
How to solve the problem of large 100A fluctuation in the output current at the fan application site of the GD5000 inverter
A: 1. Verify whether the VFD parameters are set correctly, confirm if the motor has undergone self-learning, and check the working conditions at the customer site;
2. Observe the operating data of the motor and load before and after decoupling, and confirm whether the problem is a mechanical issue on the load side or an electrical issue on the equipment side based on the observed phenomena.
3. If the no-load output is stable but regular current fluctuations occur when loaded, it is most likely a mechanical fault on the load side. It is recommended that the customer perform dynamic balance correction, and check the alignment accuracy of the coupling, bearing clearance, etc.
When the P00.09 frequency source configuration is set to B (frequency source setting), i.e., P00.09 = 1, and the P43 group sleep function is used, the system cannot enter sleep mode even when the frequency falls below the sleep threshold.
A: When using the P43 group sleep function, P00.09 must be forcibly set to 0 by default, i.e., A (frequency source setting).
1. Set the operation mode to power balance mode, and use optical fiber communication between the two main units
2. Set the droop control to 1-2 Hz to achieve dynamic power balance
3. Appropriately adjust the current loop and speed loop of the P3 vector group to ensure stable current output
These series HT3360-500K,RM20-90K(PM10-15K)RM25-600K(PM30X),RM25-200K(PM25C),RM40-500K(PM50),RM600/60D,RM600-1000K(PM100DFaults such as bus overvoltage, explosion, and output overload occur.
A: To check the "Scope" menu on the display, look at the output voltage and current waveforms. To zoom in on the current waveform, click "Zoom In" when it is displayed in Small mode.
The purpose is: to see the type of load, whether it is industrial control load, because industrial control load has energy feedback to the UPS, causing unstable operation.
The current solution is to install the BAU (discharge device
What is the difference between the STO function on GD series models equipped with STO and the coast to stop function of the S-terminal?
A: The results are the same; both STO and free stop will block the output, but STO will trigger a fault. STO is controlled by hardware circuitry, while coast to stop is controlled by software. STO offers greater safety and stability.
An emergency stop involves decelerating to a stop, but the deceleration time is based on P01.26 (Emergency Stop Time), which differs from P00.12 (Deceleration Stop Time) used for normal deceleration stops. The coast to stop immediately block the output, whereas a deceleration stop does not.
No. The AI/AO and expansion card PTC temperature measurement function of the GD350A is not Ex/ATEX certified.

Our site uses cookies to provide you with a better onsite experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie Policy.