Q : How to Troubleshoot UPS Fault Code 65 on HT(R)X 01-20KVA S L Models?
A: Applicable Model: HT(R)X 01-20KVA S L
The UPS displays fault code 65 and fails to start normally. According to the user manual, this fault indicates low battery voltage. How should we troubleshoot this issue?
When this series of UPS triggers fault code 65, the control logic will prevent normal startup. This fault is mainly caused by three factors: faulty UPS charger, damaged batteries, or abnormal battery voltage detection circuit.
Please follow the steps below to locate the root cause:
1. Check the actual battery voltage and confirm whether it matches the value displayed on the UPS screen, so as to determine whether the fault originates from the detection circuit on the power board.
* If consistent:
Disconnect the two battery BUS cables connected to the UPS power board and restart the UPS. Next, measure the DC voltage at the battery BUS cable terminals on the power board to verify whether the measured voltage is roughly equal to the reading shown on the UPS screen and check if the UPS can start normally.
NOTES: Make sure to discharge the capacitors at these terminals before disconnecting or reconnecting the battery BUS cables.
* If inconsistent:
The battery voltage detection circuit on the power board may be damaged, which requires replacement of the power board.
More Resources

Services
Learn about INVT’s global after-sales policies, service processes, and technical support commitment.

Downloads
Get product catalogs, manuals, drawings, software, certificates, and more.

Training Videos
Learn product knowledge, operation guides, and application technologies through online training videos.



Repair Progress Tracking | Identity Verification
To protect your repair information, please verify using the mobile number reserved on the service order.

Contact INVT
Get in touch with INVT. Our team will get back to you shortly.
-
Industrial Automation
-
Network Power
-
PV & ESS
-
e-Mobility