Type | In-rack liquid-to-liquid CDU | ||
Model | - | SCU015RL | SCU030RL |
Performance specifications | |||
Heat exchange capacity | kW | 15 | 30 |
Dimensions | mm | 450×850×175 (4U, excluding handles and connectors) 482×934×175 (4U, excluding handles and connectors) | |
Power input | - | 220V 1N~ 50Hz/60Hz, standard dual power supply | |
Secondary-side system specifications | |||
Rated supply liquid temperature (℃) | ℃ | 40 | |
Rated return liquid temperature (℃) | ℃ | 50 | |
Rated circulating flow rate | m³/h | 1.4 | 2.8 |
Available pump head on secondary side outlet | m | ≥10 | |
Primary-side system specifications | |||
Rated return liquid temperature (℃) | ℃ | 35 | |
Rated supply liquid temperature (℃) | ℃ | 45 | |
Rated circulating flow rate | m³/h | 1.4 | 2.8 |
Type | In-rack liquid-to-air CDU | |||
Model | - | SCU008RA | SCU016RA | |
Performance specifications | ||||
Heat exchange capacity | kW | 8 | 16 | |
Dimensions | mm | 450×850×175 (excluding handles and connectors) 482×934×175 (including handles and connectors) | 450×850×350 (excluding handles and connectors) 482×934×350 (including handles and connectors) | |
Power specifications | - | 220V 1N~ 50Hz/60Hz, standard dual power supply | ||
Secondary-side system specifications | ||||
Rated supply liquid temperature (℃) | ℃ | 45 | ||
Rated return liquid temperature (℃) | ℃ | 55 | ||
Rated circulating flow rate | m³/h | 0.9 | 1.8 | |
Available pump head on secondary side outlet | m | ≥10 | ||
Primary-side system specifications | ||||
Rated inlet air temperature (℃) | ℃ | 25 | ||