| Function description | Specification | |
| Power input | Input voltage (V) | AC 3PH 380V(-15%) – 440V(+10%); Rated voltage: 380V AC 3PH 520V (-15%) – 690V (+10%); Rated voltage: 660V |
| Input current (A) | See section 3.6 "Product ratings". | |
| Input frequency (Hz) | 50Hz or 60Hz; Allowed range: 47–63Hz | |
| Power output | Output voltage (V) | 0–Input voltage |
| Output current (A) | See section 3.6 "Product ratings". | |
| Output power (kW) | See section 3.6 "Product ratings". | |
| Output frequency (Hz) | 0–400Hz | |
| Technical control performance | Control mode | Space voltage vector control, sensorless vector control (SVC), and feedback vector control (FVC) mode |
| Motor type | Asynchronous motor (AM) and permanent magnetic synchronous motor (SM) | |
| Speed ratio | For AMs, 1:200 (SVC); for SMs, 1:20 (SVC), 1:1000 (FVC) | |
| Speed control accuracy | ± 0.2% (SVC); ± 0.02% (FVC) | |
| Speed fluctuation | ±0.3% (SVC) | |
| Torque response | < 20ms (SVC); < 10ms (FVC) | |
| Torque control accuracy | 10% (SVC); 5% (FVC) | |
| Starting torque | For AMs: 0.25Hz/150% (SVC) For SMs: 2.5Hz/150% (SVC) 0Hz/200% (FVC) | |
| Overload capacity | For heavy load applications: 150% of rated current: 60s; 180% of rated current: 10s; 200% of rated current: 1s For light load applications: 120% of rated current: 60s; 150% of rated current: 10s; 180% of rated current: 1s | |
| Running control performance | Frequency setting method | Settings can be implemented through digital, analog, pulse frequency, multi-step speed running, simple PLC, PID, Modbus communication, PROFIBUS communication and so on. Settings can be combined and the setting channels can be switched. |
| Automatic voltage regulation | The output voltage can be kept constant although the grid voltage changes. | |
| Fault protection | More than 30 protection functions, such as protection against overcurrent, overvoltage, undervoltage, overtemperature, phase loss, and overload | |
| Speed tracking restart | Enables smooth startup of a rotating motor. Note: This function is available for the 0004 and above models. | |
| Peripheral interface | Terminal analog input resolution | No more than 20mV |
| Terminal digital input resolution | No more than 2ms | |
| Analog input | 2 inputs; AI1: 0–10V/0–20mA; AI2: -10–+10V | |
| Analog output | One input; AO1: 0–10V/0–20mA | |
| Digital input | Four regular inputs; max. frequency: 1kHz; internal impedance: 3.3kΩ Two high-speed inputs; max. frequency: 50kHz; supporting quadrature encoder input; with speed measurement function | |
| Digital output | One high-speed pulse output; max. frequency: 50kHz One Y terminal open collector output | |
| Relay output | Two programmable relay outputs RO1A: NO; RO1B: NC; RO1C: common RO2A: NO; RO2B: NC; RO2C: common Contact capacity: 3A/AC250V, 1A/DC30V | |
| Expansion interface | Two expansion interfaces for 5.5kW and lower models: SLOT1 and SLOT2 Three expansion interfaces for 7.5kW and higher models: SLOT1, SLOT2, and SLOT3 Supports PG cards, programmable cards, communication cards, I/O cards and so on | |
| Others | Installation method | Supports wall mounting, floor mounting, and flange mounting. |
| Temperature of running environment | -10°C – +50°C. Derating is required when the ambient temperature exceeds 40°C. | |
| IP rating | IP20 | |
| Pollution degree | Degree 2 | |
| Cooling method | Forced air cooling | |
| Braking unit | Built-in part for 380V 0037 and lower VFD models. Optional built-in part for 380V 0045–0110 (inclusive) models. Optional external part for 660V models. | |
| EMC filter | All 380V models meet the IEC61800-3 C3 requirements. Optional external filters can be used to meet the IEC61800-3 C2 requirements. | |
IPE300 Series Engineering VFD
IPE300 series engineering VFD is a high-performance vector single-drive system oriented to engineering applications. The VFD features high reliability, usability, maintainability, environment adaptability, and wide power range, provides enriched functions, and supports flexible configuration. The VFD can be widely used in equipment driving with demanding reliability and performance requirements in industries such as non-ferrous metals, metallurgy, paper making, petroleum, chemical, HVAC water supply, municipal engineering, electric power, building material, and power supply.
Features
The VFD adopts the new Euler platform control algorithm, enabling high-torque output at low speeds. With excellent dynamic performance and strong overload capability, it can drive three-phase AC asynchronous motors and three-phase AC permanent magnet motors. It also supports user programming, PC software monitoring, communication bus, and multiple encoder types. With rich and powerful combined functions, it meets diverse engineering application needs.



Specifications
Downloads
More Resources
Have questions or need support?
Our professional team is here to help.



Repair Progress Tracking | Identity Verification
To protect your repair information, please verify using the mobile number reserved on the service order.

Contact INVT
Get in touch with INVT. Our team will get back to you shortly.
-
Industrial Automation
-
Network Power
-
PV & ESS
-
e-Mobility