Q : When should the GD5000 transformer tap be adjusted to the -5% or +5% position?
A: If the MVD input voltage is lower than the line voltage and a Grid undervoltage fault occurs, adjust the transformer tap to the -5% position. If the input voltage is too high causing an overvoltage fault in the MVD, adjust the transformer tap to the +5% position.