Q : How to Troubleshoot the “Rectifier Fail-SET / REC Soft Start Fail-SET” Alarm on RM/50X UPS?
A: The UPS displays the alarm 'Rectifier fail‑Set/REC Soft Start Fail‑SET' on the screen and the rectifier fails to start normally. How to troubleshoot this fault?
When the UPS of this series shows the alarm 'Rectifier fail‑Set/REC Soft Start Fail‑SET' on its screen, please carry out troubleshooting in accordance with the following steps:
1. Re-insert the Power Module into the cabinet again.
2. Remove the cover of the faulty UPS, and Locate the rectifier power board 17001-02401 (There are three pieces of this board in the Power Module), and test the IGBT according to the requirements . If it is damaged, replace the board and check the result.
3. Locate the input SCR board 17001-05097 , and test the fuses and SCR according to the requirements . If it is damaged, replace the board and check the result.
NOTE: These alarms cause most probably because of the INPUT and RECTIFIER power board.
4. Locate the inverter power board 17001-02549 (There are three pieces of this board in the Power Module), and test the IGBTs according to the requirements. If it is damaged, replace the board and check the result.
5. Locate the inverter busbar board 17001-02458, and test the fuses according to the requirements. If it is damaged, replace the board and check the result.
6. Check the rectifier busbar board 17001-02385 using the same method as step 5;If it is damaged,replace the board and check the result.
Alternatively, check whether a bus voltage value(Searching Way:MODULE-INFO-BUS) is displayed for this module on the UPS screen;if the voltage is displayed and within the normal range, it indicates the unit is functioning properly
7. Replace the control board 17001-02348.
Related Questions
Can the 6-20K small capacity machine UPS set 21-24 lead-acid batteries?
MTR V2.03C Software connection and Operation Guide: PC-to-UPS Communication & Parameter Configuration
How to Troubleshoot RMX Series UPS Module Cabinet Detection Failure?
How to Troubleshoot the “Rectifier Fail-SET / REC Soft Start Fail-SET” Alarm on RM/50X UPS?
More Resources

Services
Learn about INVT’s global after-sales policies, service processes, and technical support commitment.

Downloads
Get product catalogs, manuals, drawings, software, certificates, and more.

Training Videos
Learn product knowledge, operation guides, and application technologies through online training videos.



Repair Progress Tracking | Identity Verification
To protect your repair information, please verify using the mobile number reserved on the service order.

Contact INVT
Get in touch with INVT. Our team will get back to you shortly.
-
Industrial Automation
-
Network Power
-
PV & ESS
-
e-Mobility