Q : What Is the Logic Behind "Regeneration Avoidance" as Described in the GD270 Brochure?
A: The basic principle applies when the outlets of two fans share the same duct. If one fan spins significantly faster than the other, the resulting pressure difference drives the slower fan to accelerate until its speed matches that of the faster fan.
At this point, the slower fan enters a generator mode, feeding energy back into the VFD and causing the VFD's DC bus voltage to rise.
If the voltage reaches the over-voltage stall threshold, the VFD controlling the slower motor automatically increases its output frequency to match the actual rotational speed.
Consequently, the fan exits generator mode and returns to motor mode; it stops generating power, and the VFD's DC bus voltage drops.