Q : GD270-200-4 reports UV fault in asynchronous motor water pump application — how to fix it?

Views : 9
2025-10-24

A: GD270-200-4, Asynchronous motor water pump Application, fault phenomenon: operation reports UV. How to solve it?

Reason analysis: 

1 The static measurement main circuit is intact and the power display is normal.
2. After starting the VFD, observe that the fan does not rotate.
3. I cannot hear the sound of the contactor when I have repeatedly powered off the VFD.
4. The resistance of the contactor coil measured is normal, and the main contact is normal.
5. After replacing the power board, the contactor still does not operate.
6. Unplug 2 fan plugs, and the DC contactor will operate normally after power on.

Solution: After replacing the fan, it runs normally under load.