Q : What are the trigger conditions for bit 9 of P17.65 on GD28 drive?

Views : 3
2025-11-21

A:  When P11.01 is enabled and a transient power-off occurs, bit 9 is set to 1 when the bus voltage is lower than the following values: 460VDC for 380VAC models; 240VDC for 220VAC models.