Q : What are the over-temperature alarm and fault thresholds for the GD5000 power units and phase-shifting transformer?
A: What are the alarm and fault temperature thresholds for the power units of the GD5000 product? What are the over-temperature alarm and fault thresholds for the phase-shifting transformer?
1. Power unit: Alarm at 75°C or higher; trip at 85°C or higher;
2. Phase-shifting transformer: Factory default is an alarm at 90°C or higher; we have observed a trip at 110°C. These values can be configured in P23.05 and P23.06.