Q : How to handle the Er-02-0G fault on the DA200A Servo?
A: Cause analysis:
1. The encoder is not connected, or the encoder connector is loose.
2. One of the encoder signal wires (U, V, W, A, B, Z phases) is broken.
3. Encoder A/B phase signals are reversed.
4. Communication interruption or data abnormality caused mainly by noise interference.
Troubleshooting measures:
1. Check whether the encoder wiring is correct and whether the connector is firmly plugged in.
2. Verify that the encoder supply voltage is normal.
3. For incremental encoders, manually rotate the motor and observe parameter R2.50 (encoder Hall UVW value). Under normal conditions, the value should cycle between 1 and 6. If it shows 0 or 7, a broken wire is indicated.
4. Reduce interference on the encoder cable by routing the encoder cable separately from the motor power cable, and connect the encoder shield wire to the drive's FG terminal at one end only.