Support

Support

FAQs Library
Q
What's the meanings of suffix -1, -2 and -6 of IVC1L modules(IVC1L-1614MAR1/IVC1L-1614MAR2/IVC1L-1614MAR6)?
2021-02-25
A

-1: with integrated 2 analog inputs and 1 analog output;
-2: with removable ternimal;
-6: with integrated 2 analog inputs and 1 analog output and removable terminal;

Q
When VFD startup, after a few secdons, dEU failure is reported. How to solve it?
2021-02-25
A

dEU is the speed deviation fault. Set the speed and detect the speed deviation. After the detection time is exceeded, the inverter will stop reporting the dEU fault. The reason may be that the load is too heavy or the rotor is blocked, which causes the speed deviation to be too large. It is necessary to check the load condition, extend the speed deviation detection time, and adjust the speed loop PI parameters according to the control mode to increase the reduced output torque.

Q
What special air compressor functions does GD300-0A have?
2021-02-25
A

Sleep and wake-up function, constant voltage control, constant temperature control, component maintenance, hardware lack phase detection, phase sequence detection, fan overload protection, fan current imbalance protection, etc.

Q
Fpr GD300-21, what is the size of the HMI? What sizes are available?
2021-02-25
A

Usually we provide 7-inch HMI, with 10-inch and 4.3-inch options.

Q
Is it possible to use a third-party HMI to connect GD300-21?
2021-02-20
A

Third-party HMI can be connected to GD300-21 through Modbus RTU communication. The communication protocol in the manual is open to customers, but the HMI program needs to be configured by the customer.

Q
How to solve the problem that no display when the GD20UL is powered on?
2021-02-20
A

If the power indicator is on, the keypad does not display,  the possible causes of the failure:
1. The power supply of the driving power board is damaged or there is a short circuit;
2. The keypad wire is not in good contact or the keypad is burnt out;
3. The main control board is damaged;

If the power indicator is not on, the possible causes of the failure are as follows:
1. No input power;
2. The fuse is broken;
3. The rectifier bridge is broken.

Q
Adjusting comfortability during startup or stop:
2021-02-20
A

Startup comfortability can be adjusted by setting the following function codes: P01.01, P01.03, P09.09, P09.10, P09.11, P03.00, P03.01, and P08.05. If the analog weighing equipment is used, startup pre-torque compensation must be adjusted. For details, refer to the descriptions of the function codes.

Stop comfortability can be adjusted by setting the following function codes: P09.15, P09.16, P03.00, P03.01, and P08.04.

Q
What is the difference between power frequency off grid inverter and high frequency off grid inverter?
2021-02-20
A

High frequency inverter has small volume, high efficiency, no isolation transformer,light weight.
Grid frequency inverter with power frequency isolation transformer, the main characteristics are strong overload capacity and load impact resistance, high reliability, but the disadvantages are large size, low efficiency and high cost.
If the load is inductive load such as motor with greater impact, it is recommended to select power frequency off grid inverter; if the load is resistive load with less impact, it is recommended to select high-frequency off grid inverter. BN series belongs to power frequency off grid inverter.

Q
Can BG achieve three-phase 220VAC output?
2021-02-20
A

Yes, non-standard software needs to be customized. Note that the three-phase 220VAC current is nearly twice as large as the 380VAC current, so it needs to be used at reduced power.

3132333435 Show:
You can also view:
Service IntroductionValue added ServiceTraining DownloadFAQsProduct Query

Product Inquiry
Name:*
Company:
Country:*
E-mail Address:*
Phone:
Content:*

Our site uses cookies to provide you with a better onsite experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie Policy.