Support

Support

FAQs Library
Q
How to troubleshoot when a power phase loss alarm appears on the INVT AC air conditioning unit screen?
2025-12-31
A

The troubleshooting steps are as follows:
1.   Check the Phase Loss Percentage Setting: Inspect the phase loss percentage setting in the power settings. The factory default is typically 70%. This alarm will trigger when the phase voltage drops below this set value.
2.  Check for Grid Voltage Fluctuations: Use a multimeter to measure the voltage between the input terminals of the circuit breaker Q1 and the neutral line. Observe if the voltage ever falls below 154V. If the voltage is below 154V, this indicates a grid fluctuation issue that needs to be addressed by the customer's facility team.
3.  Inspect Wiring on the Main Control Board: Power off the unit completely. Then, check the power detection wiring at port J31 on the main control board. Disconnect the terminal and check if the wiring connections are secure. Trace the wiring to check if the connections at the circuit breaker Q3 are loose and verify that the wire sequence is correct.
4.  Replace the Control Board: If all the above steps are checked and confirmed correct, but the issue persists, it will be necessary to replace the control board.

Q
How to troubleshoot when a fan overload alarm appears on the INVT AC air conditioning unit screen?
2025-12-31
A

The troubleshooting steps are as follows:
1.  Check the Normally Open/Normally Closed Contact Settings: First, verify if the unit's contact settings are correct. Confirm the signal feedback terminal type of the fan using the wiring diagram, and ensure it matches the DI (Digital Input) settings. Correct any discrepancies if found. (This issue commonly occurs during initial startup or after fan maintenance.)
2.  Inspect the Signal Cable Connection: Check the signal cable connections. Ensure the fan's signal feedback terminal is connected to the controller's DI1 port and that the control signal has a 0-10V output. Verify all connections are secure without any looseness.
3.  Inspect the Power Cable Connection: Check the power cable connections. Confirm the fan's power cables are correctly and securely connected, with all terminals properly tightened.
4.  Replace the Fan: If all the above steps are confirmed correct and the issue persists, proceed to replace the fan.

Q
Can the P92.36 locked-rotor protection of GD350-19 be used in open-loop control?
2025-12-31
A

GD350-19 is currently only supported for use in closed-loop control. The open-loop observer is unstable at low frequencies and not very reliable, so it is not recommended to use the locked-rotor protection in open-loop control.

Q
Common issues with UPS sampling resistor circuit malfunctions
2025-11-28
A

Q1 : What is a sampling resistor circuit? What is its function in a UPS?
* Sampling resistor circuit:
A sampling resistor circuit , also known as a current sensing circuit, is a circuit that indirectly calculates the current flowing through a branch by measuring the voltage drop across a known resistance resistor.
-  Its core principle is based on Ohm's law: 
V = I × R
- Where: 
V is the voltage drop across the sensing resistor. 
I is the current flowing through the sensing resistor (which is the current we want to measure). 
R is the resistance of the sensing resistor. 
Since the resistance value R is known, as long as the voltage V across it is accurately measured, the current I = V / R can be easily calculated .

* The role of the sampling resistor circuit in a UPS:
1. System monitoring and status diagnosis 
2. Overcurrent and short circuit protection 
3. Closed-loop control 

* Sampling resistor circuit physical diagram and circuit diagram (Figure 1 is the physical diagram on the PCB board, and Figure 2 is its circuit diagram)

2025-11-28-05.png

 Figure 1

2025-11-28-06.png

Figure 2 

Q2: What fault information will the UPS report when the sampling resistor circuit fails/the current in a certain circuit is abnormal? 
A: The UPS will report ‘Bypass Volt Detect Fail-Set’ fault (as shown in Figure 3 below).

2025-11-28-07.png

 Figure 3 

NOTE: The Figure shows '2# Bypass Volt Detect Fail-Set' fault, where 2# refers to module 2 and 0# to the bypass module. 

Q3: When the UPS reports ‘Bypass Volt Detect Fail-Set’ fault, what are the typical troubleshooting steps? 
A: When the sampling resistor circuit is faulty, the typical troubleshooting steps are as follows: 
1. Check the actual input/output values of the circuit based on the location of the fault; 
2. If the actual input/output values are normal, consider whether the detection circuit on the PCB board is faulty; (For modular UPS systems, first determine if the power module/bypass module detection circuit is faulty)

Q4: How to detect whether the sampling resistor circuit on the PCB board is faulty? 
A: The method for detecting a sampling resistor circuit fault is as follows: 
1. Locate the corresponding point on the PCB board; use the ohmmeter function (Ω) of a multimeter; touch the two points on the PCB board by the multimeter probes; check whether the resistance value is within the effective range (the deviations of resistance value will vary depending on the type of resistor) ; (The detection points are shown in Figure 4).

2025-11-28-08.pngFigure 4

Q
INVT UPS Fan Malfunctions Frequently Asked Questions
2025-11-28
A

Q1: What alarms does the UPS typically display when the fan malfunctions? A: When the fan malfunctions, the UPS will typically display "Fan Fail-Set" (as shown in Figure 1 below).

2025-11-28-01.png

Figure 1

NOTE: The Figure shows ‘0# Bypass Fan Fail Set’ fault, where ‘0#’ is the bypass module and ‘X#’ is module X.

Q2: What are the common causes when the UPS displays a "Fan Fail-Set" alarm?

A: The main causes of ‘Fan Fail-Set’ alarm on the UPS are as follows:
1) Fan/fan power cable failure
2) Fan signal cable failure (white signal cable from the fan power board to the fan)
3) Short-circuit function failure of the fan power board (the short-circuit point may vary depending on the model)
4) Fan power board failure
5) Auxiliary power board failure
6) Monitoring signal cable failure (signal cable from the monitoring board to the fan power board)
7) Monitoring board failure

Q3: What are the usual troubleshooting steps when the UPS displays 'Fan Fail-Set' alarm?
A: The usual troubleshooting steps when the UPS displays ‘Fan Fail-Set’ alarm are as follows:
1) Use a jumper cap to short-circuit the power signal interface of the fan power board, and test interfaces 1—n+1 in sequence.
If there are no alarms, it is normal. If there are alarms, the source of the fault needs to be identified. The source of the fault can be determined by replacing the fan or by interface testing (as shown in Figure 2).

2025-11-28-02.png

Figure 2

2) If the source of the fault cannot be determined in the first step, continue to check:

① Fan power supply board:
J1: Fan PWM signal and LED indicators signal, power supply (as shown in Figure 3 below)

2025-11-28-03.pngFigure 3

② Check if the auxiliary power board is faulty: If the power board is supplying power normally, its LED light will light up (as shown in Figure 4 below).

2025-11-28-04.png

Figure 4

3) If the source of the fault cannot be determined in the second step, further checks are required:
① Replace the monitoring board
② Replace the cable connecting the monitoring board to the fan power board.

Q
DA200 motor deceleration takes longer in fully closed-loop mode
2025-11-28
A

Higher values for P4.60 and P4.61 cause longer deceleration time during shutdown. Increase the position loop gain of P2.02.

Q
INVT servo keyboard keeps flashing “EcRr”
2025-11-28
A

This is the EtherCAT monitoring interface. Setting P0.15 to 0 will resolve the issue.

Q
Why can’t the PCR command clear the multi-turn position on the DA200A servo drive?
2025-11-21
A

This method cannot clear multi-turn positions. It can be used to clear accumulated absolute position feedback, accumulated commands R2.05 and R2.04. To clear multi-turn positions, use P0.71.

Q
DA200A R0.25 value does not continue increasing beyond 32,767 revolutions in multi-turn mode
2025-11-21
A

 After enabling the multi-turn mode, the customer expects the R0.25 value to continue increasing beyond 32,767 revolutions, but in practice it does not increase continuously. 

Solution:

R0.25 represents the actual encoder's multi-turn value. This 16-bit value is hard-coded and cannot be modified. However, with the multi-turn mode activated, the cumulative position feedback value stored in R2.05 persists even after power loss following a multi-turn overflow. This ensures the absolute position is preserved and not lost during power failure."

12345 Show:
You can also view:
Service IntroductionValue added ServiceTraining DownloadFAQsProduct Query

Product Inquiry
Name:*
Company:
Country:*
E-mail Address:*
Phone:
Content:*

Our site uses cookies to provide you with a better onsite experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie Policy.