XG8-15KTR
Three-Phase On-Grid Inverter

The XG8-15KTR is a three-phase on-grid inverter purpose-built for residential solar systems. Featuring two MPPT trackers, up to 98.7% efficiency, 160% DC oversizing, and a maximum string input current of 18 A, it supports high-power PV modules. Combining high energy yield, comprehensive safety protection, and smart O&M, it ensures efficient, stable, and worry-free home solar generation.

·Power Range: 8~15kW
· No. of MPPT Trackers: 2
· Max. String Input Current: 18A
  • XG8-15KTR
Three-Phase On-Grid Inverter
  • XG8-15KTR
Three-Phase On-Grid Inverter
  • XG8-15KTR
Three-Phase On-Grid Inverter
ImagesImages
  • XG8-15KTR
Three-Phase On-Grid Inverter
  • XG8-15KTR
Three-Phase On-Grid Inverter
  • XG8-15KTR
Three-Phase On-Grid Inverter
Overview
Features
Specifications
Downloads
More Resources
Case
Videos
More

Features

High Energy Yield
2 MPPT trackers for efficient power generation under challenging conditions
160% DC oversizing to maximize system potential
Up to 98.7% efficiency for higher energy yield
01
Wide Compatibility
Max. 18 A input current per string, supporting high-power PV modules
Wide 180–1000 V operating range for flexible system configuration
8–15 kW power range for diverse residential applications
02
Safe & Stable
IP66-rated for reliable operation in harsh outdoor environments
Type II surge protection on both AC and DC sides to reduce lightning damage risks
Optional AFCI for fast DC arc-fault detection and shutdown
03
Smart O&M
Smart I-V diagnosis to pinpoint string faults
Fault waveform recording to capture AC-side voltage and current waveforms
RS485 standard, with optional Wi-Fi / GPRS / Ethernet, for remote monitoring
04

Specifications

 

XG8KTR-S

XG9KTR-S

XG10KTR-S

XG11KTR-S

XG12KTR-S

XG15KTR-S

Input DC (PV)

Max. input voltage

1100V

Start-up voltage

160V

200V

MPPT voltage range

180V ~ 1000V

Max. input current per MPPT

18A

Max. short circuit current per MPPT

25A

MPPT number / Strings per MPPT

2 / 1

Output AC (Grid)

Rated output power

8kW

9kW

10kW

11kW

12kW

15kW

Max. active output power

8.8kW

9.9kW

11kW

12.1kW

13.2kW

16.5kW

Max. apparent output power

8.8kVA

9.9kVA

11kVA

12.1kVA

13.2kVA

16.5kVA

Rated output current

11.5A

13A

14.4A

16.9A

17.3A

21.7A

Max. output current

12.8A

14.4A

15.9A

17.5A

19.1A

23.9A

Rated grid voltage

220V/380V, 230V / 400V

Grid connection type

3L / N / PE

Rated grid frequency/ grid frequency range

50Hz / 45~55Hz;60Hz/55~65Hz

Power factor range

0.8 leading ~0.8 lagging

THDi

< 3% ( Rated Power, Resistive Load )

Efficiency

Max. efficiency

98.7%

EU efficiency

98.5%

MPPT efficiency

99.9%

Protection

AC short-circuit protection

Yes

AFCI protection

Optional

Integrated DC switch

Yes

Residual current protection

Yes

Insulation resistance monitoring

Yes

String current monitoring

Yes

Surge protection

TYPE III(DC)/ TYPE III(AC)

General Data

Dimensions (W × H × D)

481 x 395 x 195 mm

Weight

Approx.13.5kg

Topology

Transformerless

Night self-consumption

< 1W

Operating temperature/ humidity

-25℃ ~60℃ / 0%~100% (Non-condensing)

Ingress protection rating

IP66

Noise emission (typical)

< 35dB (A)

Display

LCD / LED+APP

Communication interface

Standard: RS485; Optional: WLAN / GPRS / Ethernet

Cooling method

Natural cooling

Smart forced-air Cooling

Max. operating altitude

4000m

 

Grid standard1

EN 50549-2:2019,IEC 61727:2004,IEC 62116:2014,VDE-AR-N 4105:2018,DIN VDE V 0124-100(VDE V 0124-100):2020,CEI

0-21:2022,TOR Erzeuger Type A version 1.2,18 April 2022,OVE Richtlinie R25:2020,C10/C11:2021,EN 50549-1:2019,RfG:2016, NC RfG:2018,PTPiREE:2021,NTS:2021,RD 647:2020,UNE 217001:2020,UNE 217002:2020

 

Safety / EMC standards1

EN 62109-1:2010,EN 62109-2:2011,EN 62109-1:2010,EN IEC 61000-6-1:2019,EN IEC 61000-6-3:2021,

EN 62920:2017+A1:2021+A1:2020,EN IEC 61000-3-2:2019+A1:2021,EN 61000-3-3:2013+A2:2021,EN 61000-3-12:2011, EN IEC 61000-3-11:2019

 

Downloads

Have questions or need support?

Our professional team is here to help.

Inquiry
TOP
We use cookies to understand how our audience uses our site.
Our site uses cookies to provide you with a better onsite experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie policy.
Accept
Reject
Cancel