Q : When the UPS triggers an EPO alarm and enters EPO mode, how to troubleshoot the problem?

Views : 2
2026-05-15

A: 1. Hardware Check: 
① Verify if the EPO button or dry contacts have been manually operated; 
② Check if J4-1 and J4-2 on the dry contact board are shorted, and whether the shorting caps are loose or fallen off; 
③ Check if the EPO button is working properly, whether it is stuck, or if it malfunctions when pressed.

2. Software Check: Connect to the MTR software, find "ServSetting" - "Customization" - "CustomCode"; 
① Check the "LocalEpoDisable" function. If the alarm disappears, it indicates the dry contact board is damaged; 
② Check the "RemoteEpoDisable" function. If the alarm disappears, it indicates the button board is damaged;
③ If all of the above are disabled and the alarm does not disappear, it indicates the monitoring board or control board is damaged.