Q : When the UPS is connected to the rear - end isolation transformer, what are the equipment startup steps?
A: It is recommended to start the UPS in the maintenance bypass mode, then switch back to the bypass mode, and finally switch back to the main circuit. In this way, the impact current generated during the startup of the transformer on the UPS can be reduced.