Q : How to use the MTR monitoring software to calibrate the data of the UPS output?
A: 1. First, send the MTR 2.03.01C version to the customer. This version has an output calibration function.
2. Select the appropriate communication protocol and use RS232 or RS485 to connect the MTR to the UPS.
3. After the connection is successful, select "DetectAdjust-Mod Adjust" to calibrate the module; select "Cab Adjust" to calibrate the output of the cabinet.
4. When measuring the output voltage data, select the DC + AC mode to measure the DC component in the output. For the other measurement data, simply choose the corresponding mode.
5. Enter the actual measured data into the "Measure" column of the MTR software, and then
click "Adjust" to complete the calibration.
Note: When the calibration module outputs, it is necessary to measure and calibrate each individual module in sequence. Only after completing the separate measurements and calibrations of all modules can the modules be put into operation.