Q : UPS have the alarm of Power Share Fail-Set?
A: A: (The common cause of this fault is usually the problem with the cabinet.)
1. Check if the UPS parallel parameters are set properly.
2. Check if the jumpers on the UPS's parallel board are set according to the actual number of parallel units of the equipment.
3. Apply a small load to the UPS, then use a clamp meter to check if there is a significant discrepancy between the UPS output current and the current displayed on the screen, so as to determine whether the current transformer in the cabinet is abnormal. If the current is abnormal, power off the UPS completely, and use a multimeter to check the continuity of the current transformer pins in the cabinet to verify whether it is functioning properly.
4. Insert a module that can work normally into the cabinet, but if this alarm still occurs, it is recommended to replace the monitoring board of the cabinet.
5. If it is determined that the problem lies in the power module, first check the output board of the module. If there is no issue with the output board of the module, please replace the control board of the module.
More Resources

Services
Learn about INVT’s global after-sales policies, service processes, and technical support commitment.

Downloads
Get product catalogs, manuals, drawings, software, certificates, and more.

Training Videos
Learn product knowledge, operation guides, and application technologies through online training videos.



Repair Progress Tracking | Identity Verification
To protect your repair information, please verify using the mobile number reserved on the service order.

Contact INVT
Get in touch with INVT. Our team will get back to you shortly.
-
Industrial Automation
-
Network Power
-
PV & ESS
-
e-Mobility