Q : UPS have the alarm of Capacitor Expired-Set or Fan Expired-Set?

Views : 2
2026-05-08

A: 1. Connect the equipment to the MTR software and make changes to the maintenance period of the power module's capacitors/fans in the "Service Settings" -> "System Settings".

2. Users can use the V1.98C version of the MTR software. In the controlCmd function (password: 12345678) -> Module Operation Command Menu, select the corresponding module and clear the working time of the electrolytic capacitors/fans in the power module.