Q : How to troubleshoot a UPS alarm "Relay Short Circuit"?
A: 1. First, check if the relay is functioning correctly.
① Check the relay terminals according to the service manual. Under power-off conditions, it should be in an open circuit state; otherwise, it may be stuck together.
② Power on the UPS. With the rectifier starting but the inverter not yet fully running, under normal circumstances, there should be inverter voltage but no output voltage or a very small value. Otherwise, a short circuit exists.
2. Check for other accompanying alarms. Check if the inverter IGBT and bypass SCR are functioning correctly.
3. Check if the signal cables between the output board and the control board are properly connected. Try unplugging and replugging them.
4. The voltage sampling or operational amplifier function on the control board may be faulty.
Solution:
1. It is recommended to replace the output board first.
2.If the alarm persists, it is recommended to replace the signal cables and the control board.
(When replacing the control board, take precautions against static electricity and apply hot melt glue to the signal cable connections.)
More Resources

Services
Learn about INVT’s global after-sales policies, service processes, and technical support commitment.

Downloads
Get product catalogs, manuals, drawings, software, certificates, and more.

Training Videos
Learn product knowledge, operation guides, and application technologies through online training videos.



Repair Progress Tracking | Identity Verification
To protect your repair information, please verify using the mobile number reserved on the service order.

Contact INVT
Get in touch with INVT. Our team will get back to you shortly.
-
Industrial Automation
-
Network Power
-
PV & ESS
-
e-Mobility