Q : How to solve the problem of abnormal communication of the PIS301 self-developed SNMP card?

Views : 2
2026-01-14

A: The logical steps for the check are as follows:

1.The SNMP card address cannot be found:
a. It might be that the SNMP card or the machine slot is damaged. You can verify this by repeatedly plugging and unplugging the SNMP card, replacing the machine slot, or updating with a new SNMP card.
b.Check if the network cable is in good condition
c.Check whether there are any issues with the rear connection of the SNMP card slot.
d.The fuse on the monitoring board is damaged. Use 232 to connect the MTR software to check if it works. If the connection is successful, it indicates that the fuse is in good condition. If it fails, it means the fuse is damaged.

2. If the SNMP card address can be found but communication still fails:
a.Check if there are any issues with the communication protocol, baud rate, etc. Try to make the computer network segment and the SNMP card network segment as consistent as possible.