Q : How to reduce output reactor overheating on IPE300 VFD for long-cable asynchronous motor applications?

Views : 2
2025-10-31

A: Model : IPE300

Application condition: asynchronous motor long cable application. 

Fault phenomenon: Some output reactors have a temperature of 90℃, while the reactors change color. 

How to solve it?

Cause analysis: 

Check the motor cable for approximately 100-400 meters. Check that the carrier frequency of theVFD is set to 3-8kHz. Check the nameplate of the reactor to see if it is suitable for a carrier frequency of 2kHz. 

Solution: 

Optimize the carrier frequency of the VFD and reduce it to 2kHz for carriers with severe heating. 

Improvement effect: 

Reduce the temperature of the output reactor from 90℃ to 60 ℃