Q : Open-loop running sequence:
A: 1. After receiving the FWD and MS1–MS3 commands from the controller, the inverter sends thecontactor close command and outputs the running signal.
2. With the delay of T2 after receiving the running command, the inverter starts to accelerate tothe start frequency set in P01.01.
3. After accelerating from the start frequency to the braking frequency (P08.14), the inverter sends the brake open signal with the delay of T3 (P08.05, brake open delay).
4. After the brake is open, the inverter accelerates to the reference speed.
5. After the controller switches off the speed command (MS1–MS3), the inverter decelerates to stop according to the S curve. When the frequency reaches P08.14 (stop braking frequency), the inverter outputs the brake close command with the delay of T4 (P08.04, brake close delay), requiring the controller to remove the running command.
6. After receiving the stop command sent by the controller, the inverter stops output with the delay of T5 (P08.15), and the running signals are cancelled. After the delay of T6 (P08.28), the contactor is opened, and the running process ends.
More Resources

Services
Learn about INVT’s global after-sales policies, service processes, and technical support commitment.

Downloads
Get product catalogs, manuals, drawings, software, certificates, and more.

Training Videos
Learn product knowledge, operation guides, and application technologies through online training videos.



Repair Progress Tracking | Identity Verification
To protect your repair information, please verify using the mobile number reserved on the service order.

Contact INVT
Get in touch with INVT. Our team will get back to you shortly.
-
Industrial Automation
-
Network Power
-
PV & ESS
-
e-Mobility