Q : Why the medium voltage VFD (MVD) drive motor when running at 25-35Hz some times the ouput current vibration is huge?

Views : 2
2022-08-24

A: Because when MVD drive motor running at 25-35Hz,the speed of the motor and load reach at resonance frequency point,so the MVD output current vibration is huge. At this time, we can setting jumping frequency to aviod this resonance frequency point.