Q : How can I resolve the issue of running the GD350 directly from a specific frequency?
A: To enable the inverter to start directly from a specific frequency, configure the settings as follows:
Start-up Mode Configuration:
· Select the ‘Direct Start’ mode in function code P01.01 (set to 0)
· Set function code P01.02 (Direct Start Start Frequency) to the desired specific frequency
Frequency Command Configuration:
· Select the frequency command source via function code P00.06, configurable as Function Code Setting (0) or Analogue Setting (1-4)
· If Function Code Setting is selected, set the operating frequency to the specific value via P00.13
Control Mode Verification:
· Ensure the operating command channel (P00.01) is set to the correct control mode (e.g., Local Control, Communication Control)
· Upon receiving the run command, the drive will start directly from the specified frequency
This start method is suitable for applications requiring rapid attainment of a specific rotational speed. The drive will commence output directly from the set frequency without accelerating from 0Hz.
More Resources

Services
Learn about INVT’s global after-sales policies, service processes, and technical support commitment.

Downloads
Get product catalogs, manuals, drawings, software, certificates, and more.

Training Videos
Learn product knowledge, operation guides, and application technologies through online training videos.



Repair Progress Tracking | Identity Verification
To protect your repair information, please verify using the mobile number reserved on the service order.

Contact INVT
Get in touch with INVT. Our team will get back to you shortly.
-
Industrial Automation
-
Network Power
-
PV & ESS
-
e-Mobility