Q : GD350 in closed loop control, the feedback frequency changes a lot?

Views : 2
2022-08-22

A: Fiirst, please check the closed-loop setting parameters are ok, according to the guide of operation manual. Then do below steps:

1. Please check P20.05=0x33 or not;
2. P20.11, do auto-tuning;
3. Check that the connection between encoder and motor is normal or fixed;
4. Try to fix the motor to test, and observe the output current;
5. Please set the speed to 30 or 40Hz to see the performance.