Q : For GD100-PV, how to solve the problem of ETH1/ETH2?

Views : 2
2022-08-23

A: ETH failure means that the drive board has a short-circuit to ground or the current detection circuit is partially damaged.
-1. First, the inverter restores the factory settings, P00.18=1. Reset the motor parameters P02.01-P02.05.To see whether it will work.
-2. Try to replace the control board 34PIN horn cable or control board.
If the problem is still not resolved, the driver board needs to be replaced.