Q : How to fix output phase loss on GD350-055G-4 driving an asynchronous motor?

Views : 2
2025-10-24

A: GD350-055G-4, 

Application: asynchronous motor ordinary speed regulation

Fault phenomenon: output phase loss reported after running for a period of time. 

How to solve it?

Cause analysis: 

Check that there are no abnormalities in the motor and the cables connecting the VFD to the motor. Measure the abnormality of the VFD main circuit. Disassemble and inspect the W-phase plastic shell for melting and discoloration of the copper bars. Continuing the inspection, it was found that one screw of the W-phase copper bar was loose. 

Solution: 

Replace with new components IGBT, copper bars, and chassis. 

Improvement effect: Running normally.