Q : How to fix occasional communication disconnections on GD350-5RG-4 VFDs driving asynchronous motors?

Views : 2
2025-10-24

A: GD350-5RG-4

Application condition: Ordinary speed regulation of asynchronous motor.

Fault phenomenon: More than 20 GD350 products have a power between 4kW-90kW. During debugging, it was found that some VFDs occasionally communicate normally and occasionally disconnect. 

How to solve it?
Reason analysis: 

Check that the communication related parameters of the VFD are set correctly. The communication between the upper computer and a single VFD is normal. Check the wiring for all VFDs using a set of chrysanthemum connections. Check that the terminal resistance is normal and that the communication line shielding layer is grounded properly. 

Solution: 

Change more than 20 VFDs to three sets of chrysanthemum shaped connections.

 Improvement effect:

 Communication is normal and there are no further disconnections. 