Q : In EC160A VFD, the cooling fan runs continuously after power-on while the drive operates normally. Is this normal?

Views : 2
2026-04-10
A: In this condition, check the driver board—specifically the Q3 transistor. A faulty Q3 transistor can cause the cooling fan to run continuously even without a RUN command.
After replacing the defective component, the drive operates normally and the fan behavior returns to standard logic.