Q : Common issues with UPS sampling resistor circuit malfunctions

Views : 2
2025-11-28
A: The UPS will report ‘Bypass Volt Detect Fail-Set’ fault (as shown in Figure 3 below).

2025-11-28-07.png

 Figure 3 

NOTE: The Figure shows '2# Bypass Volt Detect Fail-Set' fault, where 2# refers to module 2 and 0# to the bypass module. 

Q3: When the UPS reports ‘Bypass Volt Detect Fail-Set’ fault, what are the typical troubleshooting steps? 
A: When the sampling resistor circuit is faulty, the typical troubleshooting steps are as follows: 
1. Check the actual input/output values of the circuit based on the location of the fault; 
2. If the actual input/output values are normal, consider whether the detection circuit on the PCB board is faulty; (For modular UPS systems, first determine if the power module/bypass module detection circuit is faulty)

Q4: How to detect whether the sampling resistor circuit on the PCB board is faulty? 
A: The method for detecting a sampling resistor circuit fault is as follows: 
1. Locate the corresponding point on the PCB board; use the ohmmeter function (Ω) of a multimeter; touch the two points on the PCB board by the multimeter probes; check whether the resistance value is within the effective range (the deviations of resistance value will vary depending on the type of resistor) ; (The detection points are shown in Figure 4).

2025-11-28-08.pngFigure 4

Have questions or need support?

Our professional team is here to help.

Inquiry
TOP
We use cookies to understand how our audience uses our site.
Our site uses cookies to provide you with a better onsite experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie policy.
Accept
Reject
Cancel