Q : Analog tracking running:

Views : 2
2022-08-25

A: This running mode indicates that the speed command is provided by analog input, the inverter  passively runs based on the analog signal as provided, the lift running curve is determined by the analog change curve generated by the external controller, and the inverter is responsible for driving the motor to run. The analog tracking running input channel must be provided by AI1 (P00.03=5).

Note:
• During analog tracking running, the inverter internal S curve does not work, the S curve of lift running is generated by the lift controller. Adjusting P05.17 or P05.22 impacts the sensitivity of analog input.
• Great analog change ratio will cause inverter running frequency transient, which may result in inverter overcurrent or overvoltage.