Q
How can I adjust the analog input on the GD5000-A0000-10-L-07 when the frequency is detected inaccurately?
2026-09-24
A

When using the analog input to control the frequency, the system fails to detect 10Hz. If set to 10Hz, the AI shows 0%; if set to 25Hz, the AI shows 32%; if set to 40Hz, the AI shows 87%; if set to 50Hz, the AI shows 99%. How should it be adjusted?

A: In the MVDP5 group parameters, select to adjust the accuracy of AI1 to control the accuracy of the analog input.

Q
GD5000 inverter input voltage is lower than the customer's site voltage, causing grid undervoltage and fault shutdown
2026-07-18
A

1. Check whether the voltage of the switchgear at the front end of the inverter is normal
 2. Check whether the inverter input voltage coefficient is normal; the default is 100%. 
3. Check whether the voltage detection board is working properly and verify its specifications and model
 4. If the actual measured voltage matches the customer's on-site voltage, adjust the input voltage detection coefficient to keep the inverter and the customer's site voltage consistent, avoiding system misidentification of undervoltage and accidental tripping


Q
What are the common faults of the GD5000 entire machine?
2026-01-14
A

 ① Access control failure: The contact points of the access control switch are broken, or the S3 interface of the system IO board is faulty.
② Overheating of the phase-shifting transformer: The direction of the fan is incorrect, the temperature controller gives a false alarm, or there is too much dust in the environment.
③ Bypass cabinet action failure: The manual/automatic type setting is incorrect, or the address setting is wrong.
④ Buffer cabinet failure: The buffer contactor or the system IO board is faulty.
⑤ Frequency converter overload: The selected model is too small; the grid voltage is too low; the parameter setting is incorrect; the current detection circuit is faulty.

Q
Can GD5000 VFD be used for complete container scheme?
2022-08-25
A

GD5000 VFD can be used for the whole machine container scheme, the standard IP level is IP54; Special IP class needs to be confirmed with INVT manufacturer.

Q
How to select GD5000 VFD for the mixer used in rubber industry?
2022-08-25
A

The load of the mixer requires 150% current to last for 1 minute, so the selection of VFD is 1.66 times larger than the motor.

Q
How to select GD5000 VFD in sugarcane press applications?
2022-08-25
A

For the whole sugarcane mill line, located in the first press, the selection of the motor magnification 1.4 times, the remaining VFD magnification 1.2 times.

Q
Does the GD5000 VFD have a power cell pre-charging circuit?
2022-08-24
A

The GD5000 power cells don't has pre-charging circuit, but the whole VFD has a buffer circuit, which can pre-charge and buffer the cells.

Q
The HMI of GD5000 appears blue screen and a gold finger interface during operation?
2022-08-24
A

The main interface cannot be accessed

First, determine the model of HMI. If it is TPC1062KI mode, it is a hardware problem. If it is TPC1061TH mode, first write HMI program to try. If the problem can not be solved, need to replace the HMI.

Q
Can the GD5000 be equipped with gear switch cabinets and soft starters?
2022-08-24
A

According to customer's requirements, we can supply  gear switch cabinets and  soft starters.

12345 Show:
You can also view:
Service IntroductionValue added ServiceTraining DownloadFAQsProduct QueryReport a Vulnerability

Product Inquiry
Name:*
Company:
Country:*
E-mail Address:*
Phone:
Content:*

Our site uses cookies to provide you with a better onsite experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie Policy.