What's the meaning of battary AH?
2020-09-23
A

AH is the capacity of battary. The relationship between battary capacity and power quantity is as below: 1kWH=1000W*H=1000V*AH(V: voltage; A: Current; H: hour)

Q
For BG series, how to generate more electricity of your solar plant in summer?
2020-09-23
A

1.Keep cooling of all component,such as panels,distribution box,inverter.A water spray cooling device can be installed around the components.

2.Set up a sunshade for inverter.When installing inverters and distribution boxes, it is better to install them in places with sunshade and rain shelter.

Q
What programming language can AX70 sereis medium PLC software Codesys support?
2020-09-23
A

IL, ST, FBD, LD, CFC, SFC

Q
How many axis can medium PLC AX70 support?
2020-09-23
A

32.

Q
What's he highest operating temperature of the MVD GD5000?
2020-09-23
A

The maximum operating temperature of IGBT is 85 ℃.The maximum operating temperature of the phase-shifting transformer is 110℃

Q
What is the GD5000's maximum rated current of power unit?
2020-09-23
A

The current maximum power unit rating is 722A

Q
How to solve the problem of GD10's LED keypad showing "8.8.8.8.8" while power on?
2020-09-23
A

The possible causes of this failure are:
1. The keypad is damaged or the keypad cable is not connected properly, so the keypad and keypad cable can be replaced and powered on again;
2. If the control board fails, the control board can be replaced and powered on again;
3. The connection line of the drive board is not in good contact, so it can be re connected and powered on;
4. The power supply of the drive board fails, and the power supply of the drive board can be replaced.

Q
How to solve GD10's overload problem?
2020-09-23
A

In the operation of the motor, the running current exceeds the rated value but is less than the over-current limit value, and the operation time is longer, which is called overload.

The basic characteristics of overload are: Although the current exceeds the rated value, the excess amplitude is not large, and generally does not form a large impact current (otherwise, it will become an over-current fault). Another significant feature of overload is that there is a time accumulation process. When the accumulation time reaches, the overload fault is reported.

Solution: Check the VFD's power/current is bigger than the load or not.

Q
How to solve the problem that inverter interferes with external equipments?
2020-09-23
A

Make sure that the grounding is good. And use shielded cables, separate power cables and control cables, or add EMC filters or magnetic rings.