Can GD200A-2R2G-4 be used in single-phase 220 or 3-phase 220 input? What should I pay attention to?
2020-10-15
A

The minimum working voltage of 380V inverter switching power supply is 250V, We usually do not recommend using 220 V power supply to power on the 380V drive, because it will report undervoltage fault and can not run. Therefore, it is necessary to reduce the under voltage protection point in group P29, turn off the power failure and frequency reduction, and adjust the voltage points of over-voltage stall and energy consumption braking. VF control may not be a problem, if vector control is used, the performance may be reduced; the input and output current should not exceed the current marked by the original inverter.That is to say, the power should be reduced, need to derate the drive. If it is necessary to use this way in an emergency, please contact the INVT technical engineer.

Q
How to solve the problem of GD20 overvoltage stall problem?
2020-10-15
A

In the process of deceleration or stop of the inverter, due to the set deceleration time is too short or the braking capacity is not enough, the bus voltage inside the inverter is increased and protection (also known as overvoltage stall) occurs. As a result, the inverter loses the speed control of the motor. At this time, a long deceleration time should be set to keep the bus voltage in the transformer from rising too high to realize normal deceleration control. In the process of increasing speed of inverter, the set acceleration time is too short or the load is too heavy, and the grid voltage is too low, which leads to the converter over-current and protection (also known as over-current stall). When the inverter loses the speed control of the motor, a longer speed up time should be set to maintain no over-current and realize normal speed-up control.

Q
Why GD20 report motor overload (OL2) and how to solve the problem?
2020-10-15
A

The acceleration time is too short, or the motor load is too heavy, or the motor is stuck, please check above.

Q
What is the function of the DC reactor and when should I choose it?
2020-10-15
A

The DC reactor is located between the rectifier bridge and the capacitor to reduce the harmonic components in the input current, and reduce the surge current, so it can improve the power factor of the inverter. INVT GD20/GD350 series 18.5~110kW already built-in DC reactors, other series need to be equipped with external ones.

Q
What is the function of the output reactor and when should I choose it?
2020-10-15
A

The output waveform of the inverter is not a sine wave, but a PWM pulse wave. The output reactor can reduce the output harmonic, reduce the instantaneous high voltage generated when the IGBT works, and reduce the adverse effect on the insulation of the motor. The output reactor also can reduce the capacitance effect of the long cable at the output end of the inverter, avoid overcurrent of the inverter and increase the transmission distance. It is recommended that the output cable length exceeds 50m, select the suitable output reactor refer to operation manual.

Q
How to connect the inverter with computer software?
2020-10-15
A

Download the INVT Workshop or INVT Studio software on the INVT official website, connect the RS485 port of the inverter through a USB-RS485 adapter, and use the default communication parameters to connect.

Q
How to solve the problem while GD20 report overheating problem?
2020-10-15
A

Overheating is a common fault. When faced this kind of situation, we will first think about whether the cooling fan is running, whether the fan is blocked, whether the ambient temperature is too high, the inverter is not well ventilated, and the temperature detection circuit has problem.

Q
How to solve the problem while report phase-loss fault?
2020-10-15
A

The inverter can be divided into single-phase 220V and three-phase 380V(or 400V, 460V), and the input phase loss only exists in three-phase products. The main circuit of inverter, R, S and T are three-phase AC input. When one of the phases is disconnected due to the fault of fuse or circuit breaker, phase-loss failure occurs. Please check the power input cable is normal or not.

Q
How to solve the problem that no display when the VFD is powered on?
2020-10-15
A

If the DC power indicator is on, the possible causes are: the keypad is damaged or the keypad cable is not in good contact, so the keypad and keypad cable can be replaced for testing; if the power board is damaged, replace the power board; if the main control board is damaged, replace the main control board; if the DC power supply is not enough, that means the input power supply may not be connected; or the rectifier is damaged; or the fuse is damaged.