FAQs Library
Q
How to set the filter element blockage warning signal for GD300-01A?
2022-08-16
A

Connect the blocking signal to the S2~S5 digital input terminals, set the corresponding blocking signal function in P05.02~P05.05, and at the same time, it can be set as a normally open or normally closed signal.

Q
For GD300-01A, the main engine of the air compressor is a permanent magnet synchronous motor, how to set it?
2022-08-16
A

In the motor parameter setting interface, switch the motor type to synchronous motor, then input the motor parameters according to the motor nameplate, and then perform the motor parameter autotunning. Usually this setting is sufficient. If the motor does not run well after starting, you need to fine-tune the control parameters according to the manual.

Q
For GD300-01A, "Pressure signal failure" or "temperature signal failure" is displayed
2022-08-16
A

on the HMI and it cannot be started.

How to solve it?

Please check whether the signal of the pressure transmitter is wired incorrectly or damaged, and whether the temperature sensor PT100 is wired incorrectly or damaged. After the fault is removed, GD300-01A will automatically reset, display the standby state, and then ready to run.

Q
What should I do if the HMI is connected to GD300-01A and the display communication fails?
2022-08-16
A

First of all, ensure that the wiring is correct. HMI and GD300-01A are connected through RS485 interface, please refer to the wiring diagram for correct wiring;
Secondly, check whether the Modbus communication parameters (P14.00~P14.02) of GD300-01A have been modified, usually use the default value.
Finally, you can also enter the HMI setting interface to confirm whether the COM port settings are correct.

Q
For GD300-01A, how to set the component maintenance reminder function?
2022-08-16
A

In the maintenance parameter interface, you can set the maintenance time of each component. When the use time reaches the set maintenance time, the main interface will prompt maintenance information.

Q
How does GD300-01A control the intake valve of the air compressor?
2022-08-16
A

GD300-01A has built-in air compressor control logic. According to the set loading and unloading pressure, the output relay will control the solenoid valve. The 220VAC or 110VAC power supply required by the solenoid valve is also built-in, so no external connection is required.

Q
What is the overload capacity of GD300-01A?
2022-08-16
A

The overload capacity of the GD300-01A main motor is 150% for 1 minute and 120% can run continuously.

Q
What is the power supply voltage of the HMI? Do you need an external switching power supply?
2022-08-16
A

The HMI power supply voltage is 24V. GD300-01A has a built-in 24V 1A power supply for HMI, and does not require an external switching power supply. Save user costs.

Q
Which motor types of air compressors does GD300-01A support?
2022-08-16
A

Both asynchronous motors and permanent magnet synchronous motors are supported.